A fan with a resistance of 4 ohm, working voltage of 220 V, measured working current of 5 A, calculated fan input power, fan thermal power, electric energy conversion machine Energy power

A fan with a resistance of 4 ohm, working voltage of 220 V, measured working current of 5 A, calculated fan input power, fan thermal power, electric energy conversion machine Energy power


Input power P = UI = 220V * 5A = 1100W
Fan thermal power p '= I * I * r = 5A * 5A * 4 = 100W
The last question is not clear



Knife switch fuse
Many people say that in general circuits, the fuse can only be installed on the live wire, but in home circuits, the live wire and the zero wire behind the knife switch have fuse positions. I think most people have fuses installed on the live wire and the zero wire behind the knife switch, Is this not correct? Is it possible to install a fuse only behind the live wire? And the vacancy on the zero line behind the knife switch should be connected with copper wire?


In the past, it was very popular to install fuses behind the two-wire live wire and the zero wire. It seems that there is one more layer of insurance than the single fuse live wire. In fact, if the zero wire fuse is blown but the fire wire fuse is not blown, it is very unsafe and unsafe! Because at this time, the line is still